Performance ranges
  • Unit coolers capacity: from 2,22 to 8,9 kW *
  • Brine coolers and CO2 coolers: customized on demand
  • Airflow: from 950 to 4.400 m3/h
  • High heat exchange efficiency
  • Designed with special profile aluminium fins and inner grooved copper tubes
Coil features According to the room temperature, the employed fin spacing is the following:
- high temperatures (>=+2 °C): 3,5 mm
- low temperatures (>=-25 °C): 7,0 mm, with electric defrost
Standard defrost Electric (ED) 400V/3/50Hz
Casing features Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film
Fan motor features
  • Diameter: 315 mm
  • Single-phase, with external rotor and inner capacitor
  • Voltage: 230V/50-60 Hz
  • Protection grade: IP 44
  • Class of insulation: B
  • Inner thermal contact protection
  • Working temperature: from -35 °C to +40 °C
Fan guard features Manufactured from epoxy-coated steel, according to EN 294 standards
Air throw The aeraulic combination grants a considerably high air throw, measured in ECO’s Technical Lab according to CECOMAF GT6-001 standards
Testing Heat exchangers are supplied clean and tested at a pressure of 30 bars
Miscellaneous All the fan motors and electric heaters are connected in separate terminal boxes, with IP 54 protection grade
* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; refrigerant R404A; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K.