Jump to content



IDE

Air flow scheme
Performance ranges
  • Unit coolers capacity: from 5,73 to 77 kW *
  • Brine coolers and CO2 coolers: customized on demand
  • Airflow: from 3.100 to 32.400 m3/h
  • High heat exchange efficiency
  • Designed with special profile aluminium fins and the new inner grooved copper tubes
Coil features

According to the room temperature, the employed fin spacing is the following:

-IDE-4 for high temperatures (>= +2 °C): 4,5 mm
-IDE-7 for medium temperatures (>= -25 °C): 7,0 mm (electric defrost version ED recommended)
-IDE-10 for low temperatures (>= -35 °C): 10,0 mm (electric defrost version ED recommended)

Standard defrost Electric (ED) 400V/3/50Hz
Casing features Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film
Fan motor features
  • Diameter: 450 and 560 mm
  • Dual speed
  • Three-phase, with external rotor
  • Voltage: 400V/50Hz
  • Protection grade: IP 54
  • Class of insulation: F
  • Inner thermal contact protection
  • Working temperature: from -40 °C to +40 °C
Fan guard features Manufactured from epoxy-coated steel, according to EN 294 standards
Air throw The aeraulic combination grants a considerably high air throw, measured in ECO’s Technical Lab according to CECOMAF GT6-001 standards
Testing Heat exchangers are supplied clean and tested at a pressure of 30 bars
* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; refrigerant R404A; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K.


Copyright © 2012 Luvata. All rights reserved.