| Air flow scheme |
 |
| Performance ranges |
- Air cooled condensers capacity: from 125 to 1226 kW *
- Liquid coolers: customized on demand
- Airflow: from 26.600 to 292.900 m3/h
- Sound pressure level: from 32 to 60 dB A (10 m)
|
| Coil features |
- High heat exchange efficiency
- Designed with special "Air Intake" profile aluminium fins and inner grooved copper tubes
- Fin spacing: 2,1 mm
- Charge: dry air at 2 bars
|
| Casing features |
Made of a pre-painted galvanized metal sheet |
| Fan motor features |
- Diameter: 800 mm
- Three-phase, with external rotor
- Voltage: 400V/3/50Hz
- Sickle blade
- Protection grade: IP 54
- Class of insulation: F
- Internal thermal contact protection
|
| Fan guard features |
Manufactured from epoxy-coated steel, according to EN 294 standards |
| Testing |
Heat exchangers are supplied clean and tested at a pressure of 30 bars |
* Published capacity: ambient temperature = 25 °C; condensing temperature = 40 °C; refrigerant R404A (standard EN 327).