| Air throw schemes |
 |
| Performance ranges |
- Capacity: from 88,4 to 489,1 kW *
- Airflow: from 16.488 to 109.971 m3/h
- Sound pressure: from 48 to 66 dB (A) at 10 m
|
| Coil features |
- High heat exchange efficiency
- Manufactured with special profile aluminium fins and the new cross-grooved copper tubes
- Charge: dry air at 2 bars
|
| Casing features |
Made of a pre-painted galvanized steel sheet, covered by a plastic protection film |
| Fan motor features |
- Centrifugal
- Three-phase, belt-drive
- Voltage: 400V/50Hz
- Type: 18/18 outlet flange
- Internal thermal contact protection
- Protection grade: IP 55
- Class of insulation: F
- Designed for canalised installation, with an available maximum static pressure of 200 Pa
|
| Testing |
Heat exchangers are supplied clean and tested at a pressure of 30 bars |
* Published capacity: ambient temperature = 25 °C; condensing temperature = 40 °C; refrigerant R404A (standard EN 327)