| Air flow scheme |
 |
| Performance ranges |
- Cooling capacity: from 0,79 to 4,53 kW *
- Brine coolers and CO2 coolers: customized on demand
- Airflow: from 600 to 2.840 m3/h
|
|
- High heat exchange efficiency
- Manufactured with special profile aluminium fins and inner grooved copper tubes
|
| Coil features |
According to the room temperature, the employed fin spacing is the following: - high temperatures (>= +2 °C): 4,0 mm - low temperatures (>= -25 °C): 7,0 mm, with electric defrost |
| Standard defrost |
Electric (ED) 230V/1/50-60Hz |
| Casing features |
Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film |
| Fan motor features |
- Diameter: 250 mm
- Single-phase, with shaded poles
- Voltage: 230V/1/50-60Hz
- Protection grade: IP 44
- Working temperature: from -35 °C to +40 °C
- Inner thermal contact protection
- Quick cable connections
|
| Fan guard features |
Manufactured from fibreglass charged polyamide, according to EN 294 standards |
| Air throw |
The aeraulic combination grants a considerably high air throw, measured in ECO's Technical Lab according to CECOMAFGT6-001 standards |
| Testing |
Heat exchangers are supplied clean and tested at a pressure of 30 bars |
| Miscellaneous |
All the fan motors and electric heaters are connected in separate terminal boxes, with IP 54 protection grade |
* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; refrigerant R404A; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K