Jump to content



MTE

Air flow scheme
Performance ranges
  • Cooling capacity: from 0,79 to 4,53 kW *
  • Brine coolers and CO2 coolers: customized on demand
  • Airflow: from 600 to 2.840 m3/h
  • High heat exchange efficiency
  • Manufactured with special profile aluminium fins and inner grooved copper tubes
Coil features According to the room temperature, the employed fin spacing is the following:
- high temperatures (>= +2 °C): 4,0 mm
- low temperatures (>= -25 °C): 7,0 mm, with electric defrost
Standard defrost Electric (ED) 230V/1/50-60Hz
Casing features Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film
Fan motor features
  • Diameter: 250 mm
  • Single-phase, with shaded poles
  • Voltage: 230V/1/50-60Hz
  • Protection grade: IP 44
  • Working temperature: from -35 °C to +40 °C
  • Inner thermal contact protection
  • Quick cable connections
Fan guard features Manufactured from fibreglass charged polyamide, according to EN 294 standards
Air throw The aeraulic combination grants a considerably high air throw, measured in ECO's Technical Lab according to CECOMAFGT6-001 standards
Testing Heat exchangers are supplied clean and tested at a pressure of 30 bars
Miscellaneous All the fan motors and electric heaters are connected in separate terminal boxes, with IP 54 protection grade
* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; refrigerant R404A; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K