Jump to content



ICE

Air flow scheme
Performance ranges
  • Unit coolers capacity: from 10,1 to 169 kW *
  • Brine coolers and CO2 coolers: customized on demand
  • Airflow: from 3.700 to 78.750 m3/h
Coil features

Coil features 

  • High heat exchange efficiency
  • Manufactured with special profile aluminium fins and the new inner grooved copper tubes

According to the room temperature, the employed fin spacing is the following:

  • ICE 06: for more or equal -15°C room temp.
  • ICE 08 - 10 - 12: for more or equal -35°C room temp. With 8,0; 10,0 and 12,0 mm fin spacing, the electric defrost ED version is recommended
Standard defrost Electric (ED) 400V/3/50Hz
Casing features Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film
Fan motor features
  • Diameter: 450, 560 and 630 mm
  • Three-phase, with external rotor
  • Voltage: 400V/50Hz
  • Protection grade: IP 54
  • Inner thermal contact protection
  • Working temperature: from -40 °C to +40 °C
Fan guard features Manufactured from epoxy-coated steel, according to EN 294 standards
Air throw The aeraulic combination grants a considerably high air throw, measured in ECO’s Technical Lab according to CECOMAF GT6-001 standards
Testing Heat exchangers are supplied clean and tested at a pressure of 30 bars
* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; refrigerant R404A; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K.