| Air flow scheme |
 |
| Performance ranges |
- Unit coolers capacity: from 10,1 to 169 kW *
- Brine coolers and CO2 coolers: customized on demand
- Airflow: from 3.700 to 78.750 m3/h
|
| Coil features |
Coil features
- High heat exchange efficiency
- Manufactured with special profile aluminium fins and the new inner grooved copper tubes
According to the room temperature, the employed fin spacing is the following:
- ICE 06: for more or equal -15°C room temp.
- ICE 08 - 10 - 12: for more or equal -35°C room temp. With 8,0; 10,0 and 12,0 mm fin spacing, the electric defrost ED version is recommended
|
| Standard defrost |
Electric (ED) 400V/3/50Hz |
| Casing features |
Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film |
| Fan motor features |
- Diameter: 450, 560 and 630 mm
- Three-phase, with external rotor
- Voltage: 400V/50Hz
- Protection grade: IP 54
- Inner thermal contact protection
- Working temperature: from -40 °C to +40 °C
|
| Fan guard features |
Manufactured from epoxy-coated steel, according to EN 294 standards |
| Air throw |
The aeraulic combination grants a considerably high air throw, measured in ECO’s Technical Lab according to CECOMAF GT6-001 standards |
| Testing |
Heat exchangers are supplied clean and tested at a pressure of 30 bars |
* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; refrigerant R404A; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K.