Jump to content



CTE

CTE
Air flow scheme
Performance ranges
  • Unit coolers capacity: from 1,05 to 57,0 kW *
  • Brine coolers and CO2 coolers: customized on demand
  • Airflow: from 780 to 30540 m3/h
Coil features
  • High heat exchange efficiency
  • Designed with special profile aluminium fins and inner grooved copper tubes

According to the room temperature, the employed fin spacing is the following:

  • CTE H3 for high temperatures (>= +2 °C): 3,5 mm
  • CTE H4 for high temperatures (>= +2 °C): 4,0 mm
  • CTE M6 for medium temperatures (>= -15 °C): 6,0 mm (electric defrost version ED is recommended)
  • CTE L8 for low temperatures (>= -35 °C): 8,5 mm, only equipped with electric defrost (ED)
Standard defrost

Electric (ED) 400V/3/50Hz

Casing features

Made of a magnesium aluminium alloy, with a smooth finish covered by a plastic protection film
Fan motor features
  1. 250 mm diameter
    - Single-phase, with shaded poles
    - Voltage: 230V/50-60 Hz
    - Protection grade: IP 44
    - Working temperature: from -35 °C to +40 °C
    - Inner thermal contact protection
  2. 315 mm diameter
    - Single-phase, with external rotor and inner capacitor
    - Voltage: 230V/50-60 Hz
    - Protection grade: IP 44
    - Working temperature: from -35 °C to +40 °C
    - Inner thermal contact protection
  3. 350 mm diameter
    - Single-phase, with external rotor and inner capacitor
    - Voltage: 230V/1/50-60 Hz
    - Protection grade: IP 44
    - Working temperature: from -35 °C to +50 °C
    - Inner thermal contact protection
  4. 500 mm diameter
    - Three-phase, with external rotor
    - Voltage: 400V/3/50-60 Hz
    - Protection grade: IP 54
    - Working temperature: from -35 °C to +60 °C
    - Inner thermal contact protection
Fan guard features
  1. in 250 mm diameter fan motors: manufactured from fibreglass charged polyamide, according to EN 294 standards
  2. in 315, 350 and 500 mm diameter fan motors: manufactured from epoxy-coated steel, according to EN 294 standards 
Air throw The aeraulic combination grants a considerably high air throw, measured in ECO’s Technical Lab according to CECOMAF GT6-001 standards
Testing Heat exchangers are supplied clean and tested at a pressure of 30 bars 
Miscellaneous Only CTE500 has no fan motors connected

* Nominal capacity: assessed in practical operating ambient, i.e. wet conditions; R404A refrigerant; air inlet temperature = 0 °C; evap. temperature = -8 °C; ΔT = 8 K.



Copyright © 2012 Luvata. All rights reserved.